TOYOPUC Computerlink — PLC setup
Configure the JTEKT TOYOPUC controller before connecting with any Computerlink library. The Computerlink network settings are common across the supported controllers; only the engineering-tool screens differ, so the guides are split by tool generation rather than by PLC model.
A power cycle is required after every parameter change. Pass the canonical PLC profile explicitly when opening a connection — the libraries do not infer it from the PLC.
Choose your setup guide
These guides use TCP port 1025 and UDP port 1035.
| Product family | Hardware | Engineering tool | Setup guide |
|---|---|---|---|
| TOYOPUC Nano | Nano 10GX, Nano 2ET | PCwin2 | PCwin2 settings |
| TOYOPUC Plus | Plus CPU, Plus EX2 | PCwin | PCwin settings |
| TOYOPUC PC10G | PC10G-1SP, PC10G, EF10, 2PORT-EFR | PCwin | PCwin settings |
| TOYOPUC PC3J | PC3JX-D, PC3JG | PCwin | PCwin settings |
Choose a setup guide also lists the example network used by the screenshots, and explains why TCP and UDP need different peer settings on this protocol.
Shared reference pages
These pages apply to both language implementations of Computerlink.
| Page | Use it for |
|---|---|
| Computerlink Troubleshooting & Codes | PLC error codes and the first check for each. |
| Computerlink Device Ranges | Device families and ranges shared by the setup guides. |
| TOYOPUC profile parameters | Canonical profile IDs, area counts, addressing options, and verified-model status. |
| TOYOPUC area ranges | Direct, prefixed, packed, width, and step attributes per profile. |
After the PLC is configured
Start from the Getting started page for your language: .NET · Python
To confirm the settings before writing any code, use PLC Scope and keep the first check read-only.